This is historical information of device classes implemented in ModbusPLC device server.
Use this link to find the valid information.
Development status:
Released
Information status: New
Contact:
Class Description
This class has been to access WAGO/Beckhof acquired values
Families: InputOutput
Key words:
Language: Cpp
Contact:
Class interface
Attributes:
Name | Description |
---|---|
DigitalInputsSpectrum: DevBoolean | — |
DigitalOutputsSpectrum: DevBoolean | — |
AnalogInputsSpectrum: DevLong | — |
AnalogOutputsSpectrum: DevLong | — |
AI_1Scalar: DevLong | — |
AI_2Scalar: DevLong | — |
AO_1Scalar: DevLong | — |
AO_2Scalar: DevLong | — |
DynAIScalar: unknown | — |
DynAOScalar: unknown | — |
DynamicAttributeScalar: unknown | — |
Commands:
Name | Description |
---|---|
StateInput: DevVoid Output: State |
This command gets the device state (stored in its device_state data member) and returns it to the caller. |
StatusInput: DevVoid Output: DevString |
This command gets the device status (stored in its device_status data member) and returns it to the caller. |
ReadValuesInput: DevVarStringArray Output: DevVarShortArray |
Read multiple 16bits registers. Uses the pre-defined Address for each type. |
WriteValuesInput: DevVarStringArray Output: DevVoid |
The address is always related to 0 Write multiple coils (digital I/O) state. argin[0]= "DO" argin[1] = first coil address argin[2] = number of coils argin[3] = 1st coil state argin[4] = 2nd coil state ... |
Pipes:
Properties:
Name | Description |
---|---|
Modbus_nameDevString | Name of the modbus device. |
Di_addressDevShort | Address where the digital inputs are mapped |
Do_addressDevShort | Address where the digital outputs are mapped |
Ai_addressDevShort | Address where the Analog Inputs are mapped |
Ao_addressDevShort | Address where the analog outputs are mapped |
RetriesDevShort | Number of retries while trying to reconnect to PLC |
DynamicInputsNamesString[]Type | Names for the dynamic attributes created for PLC Inputs: Name1\nName2\nName3\n... |
DynamicInputsAddressesInt[]Type | Adresses of the Dynamic Attributes created for PLC Inputs: Address1\nAddress2\nAddress3\n... |
DynamicOutputsNamesString[]Type | Names of the Dynamic Attributes created for PLC Outputs: Name1\nName2\nName3\n... |
DynamicOutputsAdressesInt[]Type | Adresses for the Dynamic Attributes created for PLC Outputs: Address1\nAddress2\nAddress3\n... |
DynamicAttributesString[]Type | {AttributeName}=address(XX)[+type({AI/AO/DI/DO})] |
22 Feb 2018, DS Admin
Updated:
The device class has been updated.
You can see previous version here .
20 Apr 2017, Piotr Goryl
Updated:
The device class has been updated.
You are looking at this version now.
23 Feb 2017, Piotr Goryl
Created:
The device class has been added to catalogue.
Updated:
The device class has been updated.
You can see previous version here .
20 Apr 2017, Piotr Goryl
Updated:
The device class has been updated.
You are looking at this version now.
23 Feb 2017, Piotr Goryl
Created:
The device class has been added to catalogue.
Added by:pgoryl2
on:20 Apr 2017, 1:09 p.m.